Mitsubishi Electronics QCPU Welding System User Manual


  Open as PDF
of 1204
 
App-26
*1 : The Qn/QnH changes in processing time depending on the serial No. of the CPU module.
Top : The first 5 digits of the serial No. are "05031" or lower
Bottom : The first 5 digits of the serial No. are "05032" or higher
For the condition to be satisfied when the instruction is not executed, there is no differentiation between the
top and bottom.
Instruction Condition (Device)
Processing Time (µs)
Qn QnH QnPH
QnPRH
LDD <
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status 0.55 0.24 0.24 0.24
ANDD <
When not executed 0.39 0.17 0.17 0.17
When executed
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status
0.55 0.24 0.24 0.24
ORD <
When not executed 0.39 0.17 0.17 0.17
When executed
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status
0.55 0.24 0.24 0.24
LDD > =
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status 0.55 0.24 0.24 0.24
ANDD > =
When not executed 0.39 0.17 0.17 0.17
When executed
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status
0.55 0.24 0.24 0.24
ORD > =
When not executed 0.39 0.17 0.17 0.17
When executed
In conductive status 0.55 0.24 0.24 0.24
In non-conductive status
0.55 0.24 0.24 0.24
LDE =
*1
Single
precision
In conductive status
93 40
6.4 6.4
14.9 6.4
In non-conductive status
92 40
6.4 6.4
14.9 6.4
Double
precision
In conductive status
93 40
–– ––
14.9 6.4
In non-conductive status
92 40
–– ––
14.9 6.4
ANDE =
*1
Single
precision
When not executed 0.55 0.24 0.24 0.24
When
executed
In conductive status
93 40
6.4 6.4
14.9 6.4
In non-conductive status
92 40
6.4 6.4
14.9 6.4
Double
precision
When not executed
–– –– –– ––
When
executed
In conductive status
93 40
–– ––
14.9 6.4
In non-conductive status
92 40
–– ––
14.9 6.4
ORE =
*1
Single
precision
When not executed 0.55 0.24 0.24 0.24
When
executed
In conductive status
93 40
6.4 6.4
14.9 6.4
In non-conductive status
92 40
6.4 6.4
14.9 6.4
Double
precision
When not executed 0.55 0.24
–– ––
When
executed
In conductive status
93 40
–– ––
14.9 6.4
In non-conductive status
92 40
–– ––
14.9 6.4