Mitsubishi Electronics QCPU Welding System User Manual


  Open as PDF
of 1204
 
12-77
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.8 Error code list (6000 to 6999)
6410
[MEM.COPY EXE]
The memory copy from control system to standby
system was executed.
(This can be detected from the control system of
the redundant system.)
Collateral information
• Common Information:–
• Individual Information:–
Diagnostic Timing
• At execution of the function of copying memory
from control system to standby system
RUN:
On
ERR.:
On
CPU Status:
Continue
QnPRH
6500
[TRK. PARA. ERROR]
The file register file specified in the tracking setting
of the PLC parameter dialog box does not exist.
Collateral information
• Common Information:File name/Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset
Read the individual information of the error using
GX Developer, and check and correct the drive
name and file name. Create the specified file.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
6501
[TRK. PARA. ERROR]
The file register range specified in the device detail
setting of the tracking setting of the PLC parameter
dialog box exceeded the specified file register file
capacity.
Collateral information
• Common Information:File name/Drive name
• Individual Information:Parameter number
Diagnostic Timing
• At power ON/At reset
Read the individual information of the error using
GX Developer, and increase the file register
capacity.
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU