12-23
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2114
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP RUN
Read the individual information of the error using
the GX Developer, check the program
corresponding that value (program error location),
and make correction.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01
*3
Qn(H)
*3
QnPH
QnU
2115
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP RUN
Q00J/Q00/Q01
*3
Qn(H)
*3
QnPH
2116
[SP. UNIT ERROR]
• An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
• Instruction was executed for the A or QnA
module under control of another CPU.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP RUN
Q00J/Q00/
Q01
*3
Qn(H)
*3
QnPH
QnU
2117
[SP. UNIT ERROR]
A CPU module that cannot be specified in the
instruction dedicated to the multiple CPU system
was specified.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP RUN
2118
[SP. UNIT ERROR]
When the online module change setting is set to be
“enabled” in the PLC parameter in a multiple CPU
system, intelligent function module controlled by
other CPU using the FROM instruction/intelligent
function module device (U \ G) is specified.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed
• When performing the online module change in a
multiple CPU system, correct the program so that
access will not be made to the intelligent function
module controlled by the other CPU.
• When accessing the intelligent function module
controlled by the other CPU in a multiple CPU
system, set the online module change setting to
be “disabled” by parameter.
Qn(H)
*3
QnPH
QnU
*7
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.
*7 The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.