App-123
8
8
8
8
A
8
7
8
Appendix 3 SPECIAL RELAY LIST
(2) System information
*5: The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
*6: The relevant modules are as follows:
• The Universal model QCPU whose serial number (first five digits) is "10012" or later.
• Q13UDHCPU, Q26UDHCPU
*8: The Universal model QCPU except the Q00UJCPU.
TableApp.3.3 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM202 LED OFF command
OFF ON : LED OFF
• When this relay goes from OFF to ON, the LEDs
corresponding to the individual bits at SD202 go off
UNew
Qn(H)
QnPH
QnPRH
QnU
SM203 STOP contact STOP status • Goes ON at STOP status S (Status change) M9042
QCPU
SM204 PAUSE contact PAUSE status • Goes ON at PAUSE status S (Status change) M9041
SM206 PAUSE enable coil
OFF : PAUSE disabled
ON : PAUSE enabled
• PAUSE status is entered if this relay is ON when the
PAUSE contact goes ON
U M9040
SM210 Clock data set request
OFF : Ignored
ON : Set request
• When this relay goes from OFF to ON and after END
instruction execution of subsequent scan, clock data
stored in SD210 to SD213 are written to the CPU
module.
U M9025
SM211 Clock data error
OFF : No error
ON : Error
• ON when error is generated in clock data (SD210 to
SD213) value, and OFF if no error is detected.
S (Request) M9026
SM213
Clock data read
request
OFF : Ignored
ON : Read request
• When this relay is ON, clock data is read to SD210 to
SD213 as BCD values.
U M9028
SM220
CPU No.1 preparation
completed
OFF : CPU No.1 preparation
uncompleted
ON : CPU No.1 preparation
completed
Turned ON when access can be made to the CPU
module No.1 from the other CPU module at power-on
or reset operation. SM220 is used as interlock for
accessing the CPU module No.1 when the multiple
CPU synchronous setting is asynchronous.
S (When status
changed)
New
QnU
SM221
CPU No.2 preparation
completed
OFF : CPU No.2 preparation
uncompleted
ON : CPU No.2 preparation
completed
Turned ON when access can be made to the CPU
module No.2 from the other CPU module at power-on
or reset operation. SM221 is used as interlock for
accessing the CPU module No.2 when the multiple
CPU synchronous setting is asynchronous.
QnU
*8
SM222
CPU No.3 preparation
completed
OFF : CPU No.3 preparation
uncompleted
ON : CPU No.3 preparation
completed
Turned ON when access can be made to the CPU
module No.3 from the other CPU module at power-on
or reset operation. SM222 is used as interlock for
accessing the CPU module No.3 when the multiple
CPU synchronous setting is asynchronous.
SM223
CPU No.4 preparation
completed
OFF : CPU No.4 preparation
uncompleted
ON : CPU No.4 preparation
completed
Turned ON when access can be made to the CPU
module No.4 from the other CPU module at power-on
or reset operation. SM223 is used as interlock for
accessing the CPU module No.4 when the multiple
CPU synchronous setting is asynchronous.
QnU
*5
SM235
Online module change
flag
OFF : Online module change
is not in progress
ON : Online module change
in progress
• Turns on during online module change. (for host
CPU)
S (During online
module change)
New
QnPH
SM236
Online module change
complete flag
OFF : Online module change
incomplete
ON : Online module change
complete
• Turns ON for one scan after online module change is
complete.
• This contact point can only be used by the scan
program. (for host CPU)
S (When online
module change is
complete)
New
SM237
Device range check
inhibit flag
OFF : Device range checked
ON : Device range not
checked
• Selects whether to check a device range during
execution of the BMOV, FMOV or DFMOV instruction
(only when the conditions for subset processing are
established).
UNew
QnU
*6