App-183
8
8
8
8
A
8
7
8
Appendix 4 SPECIAL REGISTER LIST
*1: The relevant modules are as follows:
• The Universal model QCPU whose serial number (first five digits) is "10102" or later.
• Q00UJCPU, Q00UCPU, Q01UCPU
TableApp.4.13 Special register
ACPU
Special
Register
Special
Register
after
Conversion
Special
Register for
Modification
Name Meaning Details
Corresponding
CPU
D9000 SD1000
–
Fuse blown
Number of module
with blown fuse
• When fuse blown modules are detected, the first I/O number of the
lowest number of the detected modules is stored in hexadecimal.
(Example: When fuses of Y50 to 6F output modules have blown,
"50" is stored in hexadecimal)
To monitor the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1100 to SD1107 are reset to 0.)
• Fuse blow check is executed also to the output modules of remote
I/O stations.
Qn(H)
QnPH
QnU
*1
D9001 SD1001
–
Fuse blown
Number of module
with blown fuse
• Stores the module numbers corresponding to setting switch
numbers or base slot numbers when fuse blow occurred.
• For the remote I/O station, the value of (module I/O No./10H) + 1 is
stored.
Qn(H)
QnPH
D9002 SD1002
–
I/O module
verify error
I/O module verify
error module number
• If I/O modules, of which data are different from data entered, are
detected when the power is turned on, the first I/O number of the
lowest number unit among the detected units is stored in
hexadecimal. (Storing method is the same as that of SD1000.)
To monitor the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1116 to SD1123 are reset to 0.)
• I/O module verify check is executed also to the modules of remote
I/O terminals.
Qn(H)
QnPH
QnU
*1
D9005 SD1005
–
AC DOWN
counter
Number of times for
AC DOWN
• When the AC power supply module is used, 1 is added at
occurrence of an instantaneous power failure of within 20ms.
(The value is stored in BIN code.) It is reset when the power supply
is switched from OFF to ON.
Qn(H)
QnPH
QnU
*1
• When the DC power supply module is used, 1 is added at
occurrence of an instantaneous power failure of within 10ms.
(The value is stored in BIN code.) It is reset when the power supply
is switched from OFF to ON.
Qn(H)
QnPH
QnU
*1
D9008 SD1008 SD0
Self-diagnostic
error
Self-diagnostic error
number
• When error is found as a result of self-diagnosis, error number is
stored in BIN code.
Qn(H)
QnPH
QnU
*1
AJ02 I/O module
Extension base unit
Setting
switch
Stored
data
Base unit
slot No.
Stored
data
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7