Mitsubishi Electronics QCPU Welding System User Manual


  Open as PDF
of 1204
 
App-132
*1: The module whose first 5 digits of serial No. is "06082" or later.
*2: The module whose first 5 digits of serial No. is "07012" or later.
*3: The module whose first 5 digits of serial No. is "07032" or later.
*4: This applies to the CPU module of function version B or later.
*5: The module whose first 5 digits of serial No. is "04012" or later.
*6: The module whose first 5 digits of serial No. is "05032" or later.
*8: The relevant modules are as follows:
The Universal model QCPU whose serial number (first five digits) is "10102" or later.
Q00UJCPU, Q00UCPU, Q01UCPU
*9: The Universal model QCPU except the Q00UJCPU.
TableApp.3.8 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM734
XCALL instruction
execution condition
designation
OFF : Not executed by
execution condition
risen
ON : Executed by execution
condition risen
During OFF, XCALL instructions will not be executed
even if execution condition is risen.
During ON, XCALL instructions will be executed
when execution condition is risen.
UNew
Qn(H)
*1
SM735
SFC comment readout
instruction in
execution flag
OFF : SFC comment readout
instruction is
inactivated.
ON : SFC comment readout
instruction is
activating.
Turns on the instructions, (S(P).SFCSCOMR) to
read the SFC step comments and (S(P).
SFCTCOMR) to read the SFC transition condition
comments.
S (status change) New
Qn(H)
*2
QnPH
*3
QnPRH
*3
SM738
MSG instruction
reception flag
OFF : Instruction not
executed
ON : Instruction execution
Goes ON when MSG instruction is executed
S (Instruction
execution)
New
Qn(H)
QnPRH
SM750
Scaling instruction
search method setting
OFF : Search next
ON : 2-part search
Determines a search method when the scaling
instruction is executed.
UNew
QnU
*8
SM774
PID bumpless
processing
(for complete
derivative)
OFF : Matched
ON : Not matched
• Specifies whether to match the set value (SV) with
the process value (PV) or not in the manual mode.
UNew
Q00J/Q00/Q01
*4
Qn(H)
QnPRH
QnU
SM775
Selection of refresh
processing during
COM/CCOM
instruction execution
OFF : Performs link refresh
ON : Performs no link
refresh
Select whether link refresh processing will be
performed or not when only communication with the
CPU module is made at the execution of the COM
instruction.
UNew
Q00J/Q00/Q01
Qn(H)
QnPH
OFF : Performs refresh
processes other than
an I/O refresh
ON : Performs refresh set
by SD778
• Select whether to perform refresh processes other
than an I/O refresh set by SD778 when the COM or
CCOM instruction is executed.
UNew
Q00J/Q00/Q01
*4
Qn(H)
*5
QnPH
*3
QnPRH
QnU
SM776
Enable/disable local
device at CALL
OFF : Local device disabled
ON : Local device enabled
• Set whether the local device of the subroutine
program called at execution of the CALL instruction
is valid or invalid.
UNew
Qn(H)
QnPH
QnPRH
QnU
*9
SM777
Enable/disable local
device in interrupt
program
OFF : Local device disabled
ON : Local device enabled
Set whether the local device at execution of the
interrupt program is valid or invalid.
UNew
SM794
PID bumpless
processing(for
incomplete derivative)
OFF : Matched
ON : Not matched
• Specifies whether to match the set value (SV) with
the process value (PV) or not in the manual mode.
UNew
Q00J/Q00/Q01
*4
Qn(H)
*6
QnPRH
QnU