12-54
4102
[OPERATION ERROR]
In a multiple CPU system, the link direct device
(J \ ) was specified for the network module
under control of another station.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
• Delete from the program the link direct device
which specifies the network module under
control of another CPU.
• Using the link direct device, specify the network
module under control of the host CPU.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
Q00/Q01
*2
Qn(H)
*2
QnPH
QnU
*10
[OPERATION ERROR]
• The network No. or station No. specified for the
dedicated instruction is wrong.
• The link direct device (J \ ) setting is incorrect.
• The module No./ network No./number of
character strings exceeds the range that can be
specified.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
QCPU
[OPERATION ERROR]
• The specification of character string
(" ") specified by dedicated instruction cannot be
used for the character string.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
QnU
4103
[OPERATION ERROR]
The configuration of the PID dedicated instruction
is incorrect.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
Q00J/Q00/
Q01
*2
Qn(H)
QnPRH
QnU
4105
[OPERATION ERROR]
PLOADP/PUNLOADP/PSWAPP instructins were
executed while setting program memory check.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
• Delete the program memory check setting.
• When using the program memory check, delete
PLOADP/PUNLOADP/PSWAPP instructions.
QnPH
*5
4107
[OPERATION ERROR]
33 or more multiple CPU dedicated instructions
were executed from one CPU module.
■Collateral information
• Common Information:Program error location
• Individual Information:–
■Diagnostic Timing
• When instruction executed
Using the multiple CPU dedicated instruction
completion bit, provide interlocks to prevent one
CPU module from executing 33 or more multiple
CPU dedicated instructions.
Q00/Q01
*2
Qn(H)
*2
QnPH
Q00U/Q01U
Q02U
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*2 The function version is B or later.
*5 The module whose first 5 digits of serial No. is "07032" or later.
*10 The Universal model QCPU except the Q00UJCPU.