Mitsubishi Electronics QCPU Welding System User Manual


  Open as PDF
of 1204
 
12-55
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.6 Error code list (4000 to 4999)
4109
[OPERATION ERROR]
With high speed interrupt setting PR, PRC,
UDCNT1, UDCNT2, PLSY or PWM instruction is
executed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Delete the high-speed interrupt setting.
When using high-speed interrupt, delete the PR,
PRC, UDCNT1, UDCNT2, PLSY and PWM
instructions.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
Qn(H)
*3
4111
[OPERATION ERROR]
An attempt was made to perform write/read to/from
the CPU shared memory write/read disable area of
the host station CPU module with the instruction.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Read the common information of the error using
GX Developer, and check and correct the error step
corresponding to that value (program error
location).
Q00/Q01
*2
QnU
4112
[OPERATION ERROR]
The CPU module that cannot be specified with the
multiple CPU dedicated instruction was specified.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
Q00/Q01
*2
QnU
*10
4113
[OPERATION ERROR]
• When the SP.DEVST instruction is executed, the
number of writing to the standard ROM of the day
exceeds the value specified by SD695.
• The value outside the specified range is set to
SD695.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
• Check that the number of execution of the
SP.DEVST instruction is proper.
• Execute the SP.DEVST instruction again the
following day or later day. Or, arrange the value
of SD695.
• Correct the value of SD695 so that it does not
exceed the range.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
QnU
4120
[OPERATION ERROR]
Since the manual system switching enable flag
(special register SM1592) is OFF, manual system
switching cannot be executed by the control system
switching instruction (SP. CONTSW).
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
To execute control system switching by the SP.
CONTSW instruction, turn ON the manual system
switching enable flag (special register SM1592).
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
QnPRH
4121
[OPERATION ERROR]
• In the separate mode, the control system
switching instruction (SP. CONTSW) was
executed in the standby system CPU module.
• In the debug mode, the control system switching
instruction (SP. CONTSW) was executed.
Collateral information
• Common Information:Program error location
• Individual Information:–
Diagnostic Timing
• When instruction executed
• Reexamine the interlock signal for the SP.
CONTSW instruction, and make sure that the SP.
CONTSW instruction is executed in the control
system only. (Since the SP. CONTSW instruction
cannot be executed in the standby system, it is
recommended to provide an interlock using the
operation mode signal or like.)
• As the SP. CONTSW instruction cannot be
executed in the debug mode, reexamine the
interlock signal related to the operation mode.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
QnPRH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*2 The function version is B or later.
*3 The module whose first 5 digits of serial No. is "04012" or later.
*10 The Universal model QCPU except the Q00UJCPU.