12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3101
[LINK PARA. ERROR]
• The system A of the MELSECNET/H remote
master station has been set to other than Station
No. 0.
• The system B of the MELSECNET/H remote
master station has been set to Station No. 0.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power ON/At reset/STOP RUN
• Set the system A of the MELSECNET/H remote
master station to Station No. 0.
• Set the system B of the MELSECNET/H remote
master station to any of Station No. 1 to 64.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnPRH
[LINK PARA. ERROR]
Since the number of points of the B/W device set in
[Device] of the PLC parameter is lower than the
number of B/W refresh device points shown in the
following table when parameters of the
MELSECNET/H are not set, the refresh between
the CPU module and the MELSECNET/H cannot
be performed.
.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power ON/At reset/STOP RUN
Set the refresh parameter of the MELSECNET/H in
accordance with the number of points of B/W
devices set in [Device] of the PLC parameter.
Qn(H)
*7
QnPH
*7
QnPRH
*7
QnU
[LINK PARA. ERROR]
The setting of the network refresh range crosses
over the boundary between the internal user device
and the extended data register (D) or extended link
register (W).
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power ON/At reset/STOP RUN
Set the network refresh range so that it does not
cross over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
No. of refresh device
points of B device
No. of refresh device
points of W device
1
8192 points
(8192 points
×
1
module)
8192 points
(8192 points
×
1
module)
2
8192 points
(4096 points
×
2
modules)
8192 points
(4096 points
×
2
modules)
3
6144 points
(2048 points
×
3
modules)
6144 points
(2048 points
×
3
modules)
4
8192 points
(2048 points
×
4
modules)
8192 points
(2048 points
×
4
modules)
Refresh
device
No. of
mountable
network
modules
*7 The module whose first 5 digits of serial No. is "09012" or later.