Mitsubishi Electronics QCPU Welding System User Manual


  Open as PDF
of 1204
 
7-276
RAD(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
The contents of the designated device or the result of the addition are not "0", or not within
the following range(For the Universal model QCPU only): (Error code: 4140)
0, 2
-126
| Contents of designated device | < 2
128
The value of the specified device is 0.
*3
(For the Basic model QCPU, High Performance model QCPU, Process CPU, Redundant
CPU) (Error code: 4100)
*3: There are CPU modules that will not result in an operation error if 0 is specified. For details, refer to 3.2.4.
The result exceeds the following range (Operation results in an overflow)
(For the Universal model QCPU only)
2
128
| Operation result | (Error code: 4141)
The value of the specified device is 0, unnormalized number, nonnumeric, and ± .
(For the Universal model QCPU only) (Error code: 4140)
Program Example
(1) The following program converts the angle set by the 4 BCD digits at X20 to X2F to radians,
and stores results as 32-bit floating decimal point type real number at D20 and D21.
[Ladder Mode]
[List Mode]
[Operations involved when X20 to X2F designate a value of 120]
Inputs an angle to be converted
into a radian value ( )
Converts the input a 32-bit
floating-point real number ( )
Converts the converted angle into
a radian value ( )
1
2
3
Step Instruction Device
X2F
BCD value
0
D0
120
X20
Conversion
to BIN
BIN
b15
b0
BIN value
120
Conversion to
floating-point
FLT
Conversion
to radian
D11 D10
RAD
D21
D20
120 2
.
094395