7.18 Other instructions
7.18.10 Reading module model name(TYPERD(P))
[Character string indicating the number of points]
• 16 points:_16
• 32 points:_32
• 48 points:_48
• 64 points:_64
• 128 points:_128
• 256 points:_256
• 512 points:_512
• 1024 points:_1024
(c) Others
• The specified slot is empty or the target module is during online module change.
• The specified value (n) is not the start I/O number.
• The specified value (n) is within the allowable setting range, but cannot be set in the
I/O assignment setting screen of the PLC parameter dialog box.
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns on, and an
error code is stored into SD0.
• The target module cannot be communicated due to a failure. (Error code: 2110)
• Devices by 10 words starting from the device specified by exceed the device range.
(Error code: 4101)
• The specified value (n) is except 0 to FF
H
and 3E0 to 3E3
H
. (Error code: 4101)
D
-1
b15 to b8 b7 to b0
00
H
00H
00H
00H
00H
00H
00H 00H
00H 00H
00H 00H
00H 00H
00H 00H
00H
00H
Stores -1.
Stores 00
H.
Indicates that the model
name is not stored.