7-292
EXP(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
• Operation results are outside the range shown below: (Error code: 4100)
2
-126
| operation result | 2
128
(For a High Performance model QCPU)
2
-126
| operation result | 2
128
(For a Basic model QCPU/Process CPU/Redundant CPU)
• The value of the specified device is 0.
*3
(For the Basic model QCPU, High Performance model QCPU, Process CPU, Redundant
CPU) (Error code: 4100)
*3: There are CPU modules that will not result in an operation error if 0 is specified. For details, refer to 3.2.4.
• The result exceeds the following range (Operation results in an overflow)
(For the Universal model QCPU only)
2
128
| Operation result | (Error code: 4141)
• The value of the specified device is 0, unnormalized number, nonnumeric, and ± .
(For the Universal model QCPU only) (Error code: 4140)