Mitsubishi Electronics Q173HCPU/Q172HCPU Work Light User Manual


 
4 - 29
4 POSITIONING SIGNALS
(5) Error reset command (M3207+20n)
(a) This command is used to clear the minor error code or major error code
storage register of an axis for which the error detection signal has turn on
(M2407+20n: ON), and reset the error detection signal (M2407+20n).
OFF
OFF
Error detection signal
(M2407+20n)
Error reset command
(M3207+20n)
Minor error code storage
register (D6+20n)
Major error code storage
register (D7+20n)
** : Error code
ON
ON
00
00
**
**
(b) If an error reset is executed during the temporary stop (M4003+10n) by the
temporary stop command (M4400+10n) at the automatic start or if an error
reset is executed during a block stop by M00/M01, the Motion program
operation state is reset.
The SVST instruction must be executed in the next strat. (Re-start is not
possible.)
Automatic start
(M4002+10n)
Temporary stop(M4003+10n)
Temporary stop command
(M4400+10n)
Block stop by M00/M01
OFF
ON
Error reset command (M3207+20n)
Start accept flag(M2001+n)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Motion program (Axis
designation program) start
(c) When the error reset command is turned on at the automatic start
(M4002+10n: ON), the above reset processing is executed after the stop
processing by temporaty stop command (M4400+10n).