Table 1.5 Positioning control error (200 to 299) list (Continued)
Control mode
Error
code
Control program
Axis designation program
(positioning)
JOG
Manual pulse generator
Home position return
OSC
Error cause
Error
processing
Corrective action
214
The manual pulse generator was enabled during
the start of the applicable axis, the manual pulse
generator operation was executed.
Manual
pulse
generator
input is
ignored
until the
axis stops.
• Execute the manual pulse
generator operation after the
applicable axis stopped.
230
When the skip is executed in the constant-speed
control, the next interpolation instruction is an
absolute circular interpolation or absolute helical
interpolation.
Immediate
stop
• Execute the absolute linear
interpolation after a point which
make a skip.
290
The override ratio is outside the range of 0 to 100[%]
during the control.
Operation is
performed
at 100[%].
• Set the override ratio within
the range of 0 to 100[%].
292
Axis interlock (M4406+10n/M4407+10n) turned on
during the control.
Decelera-
tion stop
• Turn the axis interlock
(M4406+10n/M4407+10n)
OFF in order to resume an
axis travel.