Gradient bias adjustment of analog monitor output
Here is an example of the adjustment of output from 0-20mA 20-0mA, 4-20mA using the FM terminal.
H=, H= H=, H=
20
0
100%
0
(mA)
20
0
100%
0
(mA)
4
H=, H= H=, H=
large
(mA)
20
0
0
100%
small
(mA)
20
0
0
100%
4
ŬThe analog output inclination can be adjusted using the parameter HO.
5.17 PWM carrier frequency
EH
EHEH
EH
: PWM carrier frequency
H
HH
H
: Random mode
H
HH
H
: Carrier frequency control mode selection
[Parameter setting]
Title Function Adjustment range Default setting
EH PWM carrier frequency ~kHz (~kHz) [Note 1]
According to model
Refer to page K-48.
H Random mode :Disabled, : Enabled 
H
Carrier frequency
control mode selection
:Not decrease carrier frequency automatically
:Decrease carrier frequency automatically
:Not decrease carrier frequency automatically,
400V class supported
:Decrease carrier frequency automatically,
400V class supported
:Not decrease carrier frequency automatically,
with sinusoidal filter [Note 11]
:Decrease carrier frequency automatically, with
sinusoidal filter [Note 11]
According to model
Refer to page K-48
[Note 12]
Note 1: For 200V-55/75kW models and 400V-90kW to 400V-500kW models, the carrier frequency is between 2.5
and 8.0kHz inclusive.
• Function
1) The sound tone of acoustic noise can be changed by adjusting the PWM carrier frequency. This parameter is
also effective in preventing the motor from resonating with its load machine or its fan cover.
2) In addition, this parameter reduces the electromagnetic noise generated by the inverter. Reduce the carrier
frequency to reduce electromagnetic noise. Note: Although the electromagnetic noise level is reduced, the
magnetic noise of the motor is increased.
3) The random mode reduces motor magnetic noise by changing the pattern of the reduced carrier frequency.
4) To set the parameter H to or has the effect of suppressing voltage serge to the motor. Reduce the
carrier frequency to less than 4kHz if the wiring between the inverter and motor is long (20 to 100m as a
guide).
5) In case of using the sinusoidal filter, set the parameter H to or .
This parameter works at 200V-55kW or more and 400V-90kW or more models.