Toshiba VF-AS1 Welding System User Manual


 
E6581301
E-17
5
5.9 Maximum frequency
HJ
HJHJ
HJ : Maximum frequency
Output frequency [Hz]
In case of
HJ
HJHJ
HJ
=80Hz
In case of
HJ
HJHJ
HJ
=60Hz
80Hz
60Hz
0 100% Frequency setting signal [%]
• This function determines the
maximum value in line with the
ratings of the motor and load.
• Maximum frequency cannot be
adjusted during operation. To
adjust, first stop the inverter.
ŬIf HJ is increased, adjust the upper limit frequency WN as necessary.
[Parameter setting]
Title Function Adjustment range Default setting
HJ Maximum frequency ~ Hz 
Note: The output frequency is limited to a frequency 10.5 times as high as the base frequency (XN). Even if the
maximum frequency (HJ) or the upper limit frequency (WN) is set above this frequency, this limitation is
imposed on the output frequency.Moreover, the output frequency increases up to 1.2 times the maximum
frequency (HJ) when the control that exceeds the maximum frequency (HJ) is necessary.
5.10 Upper limit and lower limit frequencies
WN
WNWN
WN : Upper limit frequency
NN
NNNN
NN : Lower limit frequency
Lower limit
frequency
0 100%
Output frequency [Hz]
WN
WNWN
WN
HJ
HJHJ
HJ
Upper limit
frequency
0 100%
Output frequency [Hz]
HJ
HJHJ
HJ
NN
NNNN
NN
Frequency
setting signal
Frequency
setting signal
Ŭ
The output frequency cannot
be set at higher than
WN
.
Ŭ
The output frequency cannot
be set at less than
NN
.
[Parameter setting]
Title Function Adjustment range Default setting
WN Upper limit frequency ~HJ Hz
Inverter with a model number ending with
-WN, HN: 
-WP: 
NN Lower limit frequency ~WN Hz 
Note: The output frequency is limited to a frequency 10.5 times as high as the base frequency (XN). Even if the
maximum frequency (HJ) or the upper limit frequency (WN) is set above this frequency, this limitation is
imposed on the output frequency.Moreover, the output frequency increases up to 1.2 times the maximum
frequency (HJ) when the control that exceeds the maximum frequency (HJ) is necessary.
• Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
• Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper limit
frequency that determines the upper limit of that frequency.