Toshiba VF-AS1 Welding System User Manual


 
K-3
E6581301
11
2. Basic parameter [3/4] Sensorless vector/vector with sensor (Ɣ:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector control
PM
control
V/f Reference
Speed
control
Torque
control
VJT
0600
Motor electronic thermal
protection level 1
10~100% 1/1 100 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 14
QNO
0017
Electronic thermal
protection characteristic
selection
Setting Motor type
Overload
protection
OL stall
1/1 0 Enabled Ɣ/Ɣ
5. 14
Ɣ Ɣ 5. 14
0
Standard
Motor
ż (protect) × (No stall)
1 ż (protect) ż (stall)
2 × (No Protection) × (No stall)
3 × (No Protection) ż (stall)
4
VF Motor
ż (protect) × (No stall)
5 ż (protect) ż (stall)
6 × (No Protection) × (No stall)
7 × (No Protection) ż (stall)
FURW
0701
Current/voltage unit
selection
0:%, 1:A (ampere)/V (volt) 1/1 0 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 15
HOUN
0005
FM terminal meter
selection
0~76 *1 1/1 0 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 16
HO 0006
FM terminal meter
adjustment
- 1/1 *4 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 16
COUN
0670
AM terminal meter
selection
0~76 *1 1/1 2 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 16
CO 0671
AM terminal meter
adjustment
- 1/1 *4 Enabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 16
EH
0300
PWM carrier frequency
1.0~16.0kHz
(2.5
~
8.0kHz)
*
2
0.1/0.1
*3
Enabled
Ɣ
/
Ɣ
Ɣ
/
Ɣ
Ɣ
Ɣ
5. 17
WXU
0301
Auto-restart control
selection
0:Disabled
1:At auto-restart after momentary stop
2:When turning ST on or off
3:1+2
4:
At start
-
up
1/1 0 Disabled Ɣ/Ɣ Ɣ/Ɣ Ɣ Ɣ 5. 18.1
WXE
0302
Regenerative power
ride-through control
0:Disabled
1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal)
4:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal+power failure)
1/1 0 Disabled Ɣ/Ɣ -/- Ɣ Ɣ 5. 18. 2
*1: For the adjustment range, see the table on page K-40.
*2: For 200V-55/75kW models and 400V-90kW to 400V-500kW models, the carrier frequency is between 2.5 and 8.0kHz inclusive.
*3: Default values vary depending on the capacity. See the table of K-48.
*4: Default setting value is adjusted for connection of frequency meters "QS60T". (Between FM and CCA: Approx. 3.6V) (Between AM and CCA: Approx. 3.6V)