6.33.18 VI/II analog input wire breakage detection level

H
HH
H : VI/II analog input wire breakage detection level
• Function
The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or moreThe
message “
G
” is displayed.
H=: Disabled ········· The detection function is disabled.
H=~ ·············· The inverter will trip if the VI/II value remains below the specified value for 0.3
seconds or more.
Title Function Adjustment range Default setting
H VI/II analog input wire breakage detection level
:None
~ %

6.33.19 Guide to time of replacement

H
HH
H : Annual average ambient temperature
• Function
You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit
capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the
output current (load factor) and the setting of
H
and that it will display and send out an alarm through
output terminals when each component is approaching the end of its useful life.
Title Function Adjustment range Default setting
H Annual average ambient temperature
: -10~+10°C
: +11~+20°C
: +21~+30°C
: +31~+40°C
: +41~+50°C
: +51~+60°C

Note 1: Using H, enter the annual average temperature around the inverter. Be careful not to enter the
annual highest temperature.
Note 2: Set H at the time of installation of the inverter, and do not change its setting after the start of use.
Changing the setting may cause a part replacement alarm calculation error.
6.33.20 Rush current suppression relay activation time
H
HH
H
: Rush current suppression relay activation time
• Function
This parameter is used to control the rush current suppressing resistor shorting relay when a direct current
is passed or multiple inverters are used with their DC sections connected to each other.
Title Function Adjustment range Default setting
H
Rush current suppression relay
activation time
~ sec. 
The rush current suppressing relay is activated on the expiration of the time limit set with parameter H after the
voltage in the DC section of the inverter has reached the specified level.