E6581301
H-7
8
[Setup values of monitor indication parameters (H~H)]
Communication
No.
Default
setting
Item displayed Marking Unit (Panel)
Unit
(Communication)
FD00 Output frequency
0.1Hz [note 4] 0.01Hz
FE02 Frequency command value
0.1Hz [note 4] 0.01Hz
FE03 Output current E
1% or FURW 0.01%
FE04 Input voltage (DC detection) [
1% or FURW 0.01%
FE05 Output voltage R
1% or FURW 0.01%
FE15 Compensated frequency
0.1Hz [note 4] 0.01Hz
FE16 Speed feedback (real-time value) 0.1Hz [note 4] 0.01Hz
FE17 Speed feedback (1-second filter) 0.1Hz [note 4] 0.01Hz
FE18 Torque S
1% 0.01%
FE19 Torque command S
1% 0.01%
FE20
Torque current Y
1% 0.01%
FE21
Exciting current E
1% 0.01%
FE22
PID feedback value 0.1Hz [note 4] 0.01Hz
FE23
Motor overload factor (OL2 data) N
1% 0.01%
FE24
Inverter overload factor (OL1 data) I
1% 0.01%
FE25
Regenerative braking resistance
overload factor (OLr data)
T
1% 1%
FE28
Regenerative braking resistance load
factor (% ED)
T
1% 1%
FE29
Input power
M
0.1kW 0.01kW
FE30
Output power J
0.1kW 0.01kW
FE39
Optional AI2 input L
1% 0.01%
FE35
RR/S4 input L
1% 0.01%
FE36
VI/II input L
1% 0.01%
FE37
RX input L
1% 0.01%
FE38
Optional AI1 input L
1% 0.01%
FE40
FM output C
1 0.01
FE41
AM output C
1 0.01
(FA65)
Communication data output [Note 3] [Note 3] [Note 3]
FE66
Attached to expansion I/O card 1 CPU version
- -
FE67
Attached to expansion I/O card 2 CPU version
- -
FE76
Integral input power
M
Depends on
H
Depends on
H
FE77
Integral output power J
Depends on
H
Depends on
H
FE00
Signed output frequency
0.1Hz [note 4] 0.01Hz
FE02
Signed frequency command value
0.1Hz [note 4] 0.01Hz
FE15
Signed compensated frequency
0.1Hz [note 4] 0.01Hz
FE16
Signed speed feedback (real-time value)
0.1Hz [note 4] 0.01Hz
FE17
Signed speed feedback (1-second filter)
0.1Hz [note 4] 0.01Hz
FE18
Signed torque S
1% 0.01%
FE19
Signed torque command S
1% 0.01%
FE20
Signed torque current Y
1% 0.01%
FE22
Signed PID feedback value 0.1Hz [note 4] 0.01Hz
FE37
Signed RX input L
1% 0.01%
FE38
Signed optional AI2 input L
1% 0.01%
FD50
Light-load high-speed load torque monitor 1
N 1% 0.01%
FD51
Light-load high-speed load torque monitor 2
J 1% 0.01%
FE31
Pattern operation group number R
0.1 0.1
FE32
Remaining no. of cycles for which
pattern operation is continued
P
1 1
FE33
Pattern operation preset speed numbers
H 1 1
FE34
Remaining time for which pattern
operation is continued
0.1 0.1
FE71
Rated voltage X
1 0.1
FE90
Rotational speed
1 1
FA15
Communication reception counter O
1 1
FA16
Communication abnormal counter P
1 1
FE43
MON1 1% 0.01%
FE44
MON2 1% 0.01%
(Continued overleaf)
[Note 2]
[Note 2]
[Note 2]
[Note 2]
[Note 2,5]
[Note 2,5]
[Note 2.5]
[Note 2]
[Note 2]
[Note 2]
[Note 2]
[Note
5]
[Note
5]
[Note
5]
[Note
5]
[Note
5]
[Note
5]
[Note
5]