Toshiba VF-AS1 Welding System User Manual


 
E6581301
D-2
4
4.1 How to set parameters
This section explains how to set parameters, while showing how parameters are organized in each setting monitor
mode.
4.1.1 Setting parameters in the selected quick mode
To place the inverter in this mode, press the
EASY
key (the LED lights up), and then press the
MODE
key.
Note that extended parameters are not displayed in the quick mode.
How to set basic parameters
(1) Selects parameter to be changed. (Press the or key.)
(2) Reads the programmed parameter setting. (Press the key.)
(3) Change the parameter value. (Press the or key.)
(4) Press this key to save the change. (Press the key.)
Adjustment range and display of parameters
JK: An attempt has been made to assign a value that is higher than the programmable range. Or, as a result of
changing other parameters, the programmed value of the parameter that is now selected exceeds the upper
limit.
NQ: An attempt has been made to assign a value that is lower than the programmable range. Or, as a result of
changing other parameters, the programmed value of the parameter that is now selected exceeds the lower
limit.
If the above alarm is flashing on and off, no setting can be done of values that are equal to or greater than JK or
equal to or lower than NQ.
ENT
ENT
Standard monitor mode
* Parameter title and the setting
value are displayed
alternately
.
*
Select key
Used to select
item
Mode key
Used to select mode
and operation level
8 kinds of standard parameter are displayed
Basic parameter setting
Enter key
Used to set values
and return to
previous menu
Quick mode (EASY)
Title Function
CW Automatic function setting
RV
V/f control mode selection
HJ
Maximum frequency
CEE
Acceleration time 1
FGE
Deceleration time 1
VJT
Motor
electronic thermal
protection level 1
HO
FM terminal meter adjustment
RUGN
Registered
p
arameter display selection