10.6 Connection of a DC power supply and other electric units
Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power
supply can be connected to the VFAS1 inverter.
When connecting each of these units, keep in mind the points described in the following sections.
10.6.1 Connection of a single-phase 200V power supply
The table below shows which model to select when operating a three-phase induction motor, using a single-phase
200V power supply (200-240V, 50/60Hz).
Input power Applicable motor (kW) Inverter type
Single phase
200~240V
50/60Hz
0.4 VFAS1-2007PL
0.75 VFAS1-2015PL
1.5 VFAS1-2022PL
2.2 VFAS1-2037PL
3.7 VFAS1-2055PL
5.5 VFAS1-2075PL
Note: Set the parameter
H
to
(input phase failure detection mode selection: disabled).
10.6.2 When using the inverter along with a DC power supply
Keep the following in mind when connecting a DC power supply to the VFAS1 (PA/+ and PC/- terminals).
Note 1: An optional initial charger (MCR-2550) is needed for middle- and large-capacity models.
Note 2: 200V-75kW and 400V-110kW or more models are needed to change the connecting for the cooling fan.
Note 3: A DC reactor does not need to be connected to the inverter.
For details about use in combination with a DC power supply, refer to the instruction manual (E6581432) specified
in section 6.42.
Voltage class Inverter model Initial charger (optional)
Change to connection of
cooling fan power supply
DC reactor
200V class
VFAS1-2004PL~
VFAS1-2150PM
No required No required No required
VFAS1-2185PM~
VFAS1-2550P
MCR-2550×1 No required No required
VFAS1-2750P MCR-2550×2 (parallel) Required No required
400V class
VFAS1-4007PL~
VFAS1-4185PL
No required No required No required
VFAS1-4220PL~
VFAS1-4900PC
MCR-2550×1 No required No required
VFAS1-4110KPC MCR-2550×1 Required No required
VFAS1-4132KPC~
VFAS1-4220KPC
MCR-2550×2 (parallel) Required No required
VFAS1-4280KPC MCR-2550×3 (parallel) Required No required
VFAS1-4355KPC,
VFAS1-4400KPC
MCR-2550×4 (parallel) Required No required
VFAS1-4500KPC MCR-2550×5 (parallel) Required No required
Note: Set the parameter
H
to
(input phase failure detection mode selection: disabled).