DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-985MAINT (EPN Maintenance Circuit Pack)
9
Error Log Entries and Test to Clear Values
Notes:
a. A value of 0 indicates that PNC-A (and therefore, the Expansion Interface
circuit pack located on PNC-A) was active when this error occurred. A
value of 1 indicates that PNC-B (and therefore, the Expansion Interface
circuit pack located on PNC-B) was active when this error occurred. To
clear this problem, make sure the Active PNC is the same as that
indicated by the Aux Value.
b. Multiple values can appear in the Aux Data field. There will be other errors
in the log if there is a real problem. Use these other errors to troubleshoot
the problem.
c. The serial link between the Expansion Interface circuit pack in the A
carrier and the EPN Maintenance circuit pack is defective.
Table 9-377. EPN Maintenance Circuit Pack Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0 Any Any Any test maintenance sh r 1
1(a) 0
1
EPN Maintenance Circuit
Pack Reset Test (#306)
MINOR ON test maintenance l
513(a) 0
1
MGR I Channel Loop
Test (#228)
MINOR ON test maintenance sh r 3
769(b) Any Sanity Handshake Test
(#106)
1537(a) 0
1
Sanity Maze Test (#303) MINOR ON test maintenance sh r 3
2561(a) 0
1
Sanity Handshake Test
(#106)
MINOR ON test maintenance sh r 3
2817(a) 0(b)
1
Serial Channel Loop
Test (#229)
MINOR ON test maintenance sh r 3
3329(c) Any Serial Link Test (#337) MINOR/
WARNING
2
2. Major and Minor alarms may be downgraded to Warning alarms based on the value used in the
set options command.
OFF test maintenance sh r 3
3585(d) Any Serial Link Test (#337) MINOR/
WARNING
2
OFF test maintenance sh r 3