DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-1184PE-BCHL (PRI Endpoint Port)
9
Error Log Entries and Test to Clear Values
Notes:
a. These error types indicate a disagreement between this switch and the
terminal adapter at the other end of the connection with regard to the
ISDN
call
state of the PRI endpoint port. This switch will automatically try
to recover by clearing the call (the call will be torn down). Use the status
pri-endpoint extension command to determine the state of the port.
When running the Short Test Sequence of tests, pay close attention to the
results of the Call State Audit Test (#257).
b. This is a software audit error that does not indicate any hardware
malfunction. Run the Short Test Sequence and investigate associated
errors.
Table 9-469. PRI endpoint port Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate test
description and follow the recommended procedures.
0 Any Any Any test port
UUCSSpp
sh r 1
1(a) Any None test port
UUCSSpp
sh r 1
15(b) Any Audit and Update Test
(#36)
18(c) 0 busyout pri-endpoint
extension
busyout port
UUCSSpp
release pri-endpoint
extension
release port
UUCSSpp
129(d) None WARNING OFF test port
UUCSSpp
sh r 1
130(e) None WARNING ON test port
UUCSSpp
sh
257(f) Any None test port
UUCSSpp
sh r 1
513(g) Any None WARNING OFF test port
UUCSSpp
sh r 1
769(f) Any None test port
UUCSSpp
sh r 1
1281(h) Any Conference Circuit Test (#7 MINOR ON test port
UUCSSpp
l r 4
1537(i) Any NPE Crosstalk Test (#6) MINOR ON test port
UUCSSpp
l r 3
1793(j) Any None test port
UUCSSpp
sh r 1
3073(k) Any Service State Audit (#256) test port
UUCSSpp
sh r 2
3585(l) Any None None