Toshiba VF-A7 Welding System User Manual


 
F-26
2) An external braking resistor (optional)
a) External braking resistor (with a thermal fuse) (optional)
[Parameter setting]
Title Function Adjustment range Setting value

Dynamic braking
mode selection
: Disabled
: Enabled/overload detection enabled
In the case that the internal dynamic resistor is used in 3.7kW model or less, then do not
use any external braking resistors. When using an external braking resistor instead of
the internal resistor, change the connection of the internal resistor from terminal PB1 to
terminal PR1. (For boosting braking force)
Do not connect an external resistor with a resistance (combined resistance) smaller
than the minimum admissible resistance.
For overload protection, be sure to set the parameters

and

properly.
[Parameter setting]
Title Function Adjustment range Setting value

Dynamic braking resistance
  [ ]

Dynamic braking resistor capacity
  [kW]
Any value
[Externally connectable braking resistors (resistance)]
Voltage
class [V]
Applicable motor
capacity [kW]
Internal braking
resistor
Minimum admissible resistance
connected externally [ ]
0.4, 0.75 63
1.5 35
2.2
120[W] - 70[ ]
25
200
3.7
120[W] - 40[ ]
17
0.75, 1.5 100
2.2 67400
3.7
120[W] - 150[ ]
40
IM
Motor
Power
supply
/
MCCB
External braking resistor
(optional)
Inverter