E-27
2) Motor 150%-overload time limit
The motor 150%-overload time limit parameter is used to set the time elapsed before
the motor trips under a load of 150% (overload trip
) within a range of 10 to 2400 seconds.
[Example: setting of ]
Monitored output
current [%]
Motor overload withstanding time [s]
(Outline data)
= =
=
=
[Hz] [Hz]
68 34 7200 3600
70 35 3600 1800
80 40 1000 500
90 45 600 300
100 50 420 210
112 56 12000 310 6000 155
120 60 2400 270 1200 135
130 65 1200 230 600 115
140 70 800 190 400 95
150 75 600 170 300 85
200 100 270 110 135 55
Title Function Adjustment range
Default setting
Motor 150%-overload time limit to [s]
3) Inverter overload characteristic
This function is provided to protect the inverter itself and it cannot be changed or
disabled by changing any parameter setting.
If the inverter overload trip function () is activated frequently, this condition can be
improved by changing the setting of the stall prevention level parameter to a
lower level or increasing the acceleration time or the deceleration time .
Inverter overload withstanding time
[s] (Outline data)
Output
current
[%]
200V:0.4
55kW
400V:0.75
75kW
200V:75,90kW
400V:90/110 280kW
111 4800 2400
120 480 240
130 240 120
140 160 80
150 120 60
160 10 9
170 4 3
180 2 0.3
215 0.5 -
If the load applied to the inverter exceeds 150% of its rated load or the
operation frequency is less than 0.1Hz, the inverter may trip in a shorter time.
Inverter's overload protective characteristic
Monitored output current [%]
Inverter overload
withstanding time
[s]
small/medium capacity types:
120
large capacity types: 60
110 150
100%: Inverter's rated output current
Monitored output current [%]
Motor 150%-overload
time limit
Motor overload
withstanding time [s]
0
0.6
1.1
1.5
Operation frequency
no less than
Operation frequency
0.01 [Hz](*1)
(*1) Except for the cases of
, [Hz]