F-45
voltage signals
current signals
6.22 Torque limit
Selection of power running torque limit #1
Power running torque limit #1
Selection of regenerative torque limit #1
Regenerative torque limit #1
Power running torque limit #2
Regenerative torque limit #2
Power running torque limit #3
Regenerative torque limit #3
Power running torque limit #4
Regenerative torque limit #4
Torque limit mode (polarity)
Note) Decreases of the output frequency are not limited by (Lower limit frequency), and
decrease up to
(Stop frequency)+0.1Hz.
Setting
(1) Power running /regenerative torque limit
First, you need to set the polarity of each torque limit. Set at .
Title Function Adjustment range Setting value
Torque limit
mode (polarity)
: Power running/regenerative torque limit
: Positive/negative torque limit
a limiting the torque with internal parameters (or on communication mode)
Torque limits can be set with the parameters and .
[Setting of power running torque]
(
Selection of power running torque limit #1
):Set at (
)
(
Power running torque limit #1
) :Set a desirable torque limit level.
[Setting of regenerative torque]
(
Selection of regenerative torque limit #1
):Set at (
)
(
Regenerative torque limit #1
) :Set a desirable torque limit level.
Function
The function is to decrease or increase the output frequency according to the load
ing condition when the motor torque reaches the limit level.
Setting a torque limit parameter at 250.0 means "Invalid".
RR-CC 0 10V (0 250%)
RX-CC 0 10V (-250 250%)
VI-CC 0 10V (0 250%)
II-CC 4(0) 20mA (0 250%)
,
250% torque
250% torque
Power running
Regenerative
Forward
Reverse
Power running
Regenerative