6.13.5 Avoiding over-voltage trip
 Over-voltage stall protection
 Over-voltage stall protection level (high response)
 Over-voltage stall protection level
[Parameter setting]
Title Function Adjustment range Default setting

Over-voltage stall protection
: Enabled, : Disabled,
: Enabled (forced quick deceleration)

Over-voltage stall protection level
(high response)
  [%] (*2)


Over-voltage stall protection level (*1)
  [%] (*2)

(*1)  serves also as the level of dynamic (regenerative) braking operation.(Refer to 6.13.4)
(*2) 100% (200V class = 200 2 [V], 400V class = 400 2 [V])
6.13.6 Adjusting the output voltage and voltage compensation
 Voltage of base frequency(output voltage adjustment)
 Selection of base frequency voltage(voltage compensation)
Voltage compensation... The V/f ratio is kept constant even at input voltage fluctuation.
Voltage limitation ... The output voltage is limited to . If the voltage compensation fun
ction is disabled, no limitation is imposed to the output voltage.
[Parameter setting]
Title Function Adjustment range Default setting

Base frequency voltage #1
(output voltage adjustment)
  [V]
 [V]
/ [V]

Base frequency voltage
(voltage compensation)
:
without voltage compensation(limitless output voltage)
:
with voltage compensation(limitless output voltage)
:
without voltage compensation(limited output voltage)
:
with voltage compensation(limited output voltage)
If  is set at or , the output voltage varies with the input voltage.
The output voltage does not exceed the input voltage, even if the base frequency voltage
() is set above the input voltage
.
Function
The functions automatically keep constant or increase the output frequency to prevent
tripping due to over-voltage in the DC bus during deceleration or constant-speed run. When
the over-volta
g
e stall protection is active, it ma
y
take lon
g
er than the deceleration time.
Function
Voltage of base frequency (output voltage adjustment)
This parameter set the base frequency  voltage. And this parameter can make it so that no
voltage exceeding the  value is put out. (This function is active when  is set or .)
Selection of base frequency voltage (voltage compensation)
The function keeps the V/f ratio constant for prevention of torque drop at low speeds
even when the input voltage drop.
Over voltage stall protection level (high response)
:

Over voltage stall protection level
:

Real deceleration time (differ from regenerative power)
DC voltage
Output frequency
Set deceleration time
Maximum frequency
If DC voltage rise and reach the level set
up by , output frequency will be
controlled in order to control this rise. If DC
voltage rise more and reach the level set
up by , this control operation is
p
erformed with hi
g
h res
p
onse.