F-60
(Disabled) does not trip (FL is not active).
(Enabled) The inverter trips if a torque larger than
(during power
running) or
(during regeneration) passes for a time
longer than the time set with
.
Title
Function
Adjustment range Default setting
Over-torque trip
: Disabled
: Enabled
Over-torque detection level during power running
[%]
Over-torque detection level during regeneration
[%]
Over-torque detection time
[s]
6.25.10 Cooling fan control mode selection
Cooling fan control mode
Automatic control of cooling fan, enabled. Operates only when the inverter is in
operation.
Automatic control of cooling fan, disabled. The cooling fan always operates
when the inverter is energized.
The cooling fan automatically operates whenever the ambient temperature is
high, even when the inverter is out of operation.
Title
Function
Adjustment range Default setting
Cooling fan control mode
: Automatic
: Always ON
6.25.11 Cumulative operation time alarm
Cumulative operation time alarm setting
Panel display of corresponds to 10 hours. If is displayed, the cumulative operation time
is 3855 hours.
Title
Function
Adjustment range Default setting
Cumulative operation time
alarm setting
[ 100h]
Output terminal setting
Ex.) Assigning the cumulative operation time alarm function to the terminal OUT2
Title
Function
Adjustment range Setting value
Output terminal selection#2 (OUT2)
Function
With this parameter, you can set the condition of cooling fan so that it operates only when
the inverter requires cooling, and thus it can be used for a longer period of.
Function
This parameter is to make a setting so that the inverter puts out a signal when it
s cumulative operation time has reached the time set with this parameter.