Toshiba VF-A7 Welding System User Manual


 
F-47
Title Function Adjustment range Default setting

Selection of power running
torque limit #1
:
VI(voltage)
/
II(current)
:
RR(volume
/
voltage)
:
RX(voltage)
:
RX2(voltage)(optional)
:


Selection of regenerative
torque limit #1
:
VI(voltage)
/
II(current)
:
RR(volume
/
voltage)
:
RX(voltage)
:
RX2(voltage)(optional)
:

The torque limit function is active in vector control mode. In V/f constant control mode, square
reduction control mode, and V/f 5-point setting mode, the torque limit function plays the same
role as the stall preventive function (6.25.2).
In torque control mode, the values set with these parameters limit torque command values.
(2) Positive/negative torque limits
First, you need to set the polarity of each torque limit. Set  at .
Title Function Adjustment range Setting value

Torque limit
mode (polarity)
: Power running/regenerative torque limit
: Positive/negative torque limit
a) Limiting the torque with parameters
RX-CC
II-CC
100
Motor torque [%]
0
0V 10V
RR-CC VI-CC
Positive
Forward
Negative
Reverse
 : Power running torque limit #1
 : Regenerative torque limit #1
Power runningRegenerative
Power running Regenerative
0V
100
-100
+10V
-10V 0
Motor torque [%]
100
Motor torque [%]
0
4mA 20mA