[5] Basic parameters #2
Vector control
Title
Communi
cation No
Function Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
To rque
control
Position
control
V/f
Constant
Reference
section
 0170 Base frequency #2 25.0 400.0 [Hz] 0.01/0.01 60.0 Enabled 6.4.1
 0171 Base frequency voltage #2 0.0 600.0 [V] 0.1/0.1 See J-28 Enabled 6.4.1
 0172 Manual torque boost #2 0.0 30.0 [%] 0.1/0.01 See J-28 Enabled 6.4.1
 0173
Motor overload protection level #2
10 100 [%] 1/0.01 100.0 Enabled 6.4.1
 0174 Base frequency #3 25.0 400.0 [Hz] 0.01/0.01 60.0 Enabled 6.4.1
 0175 Base frequency voltage #3 0.0 600.0 [V] 0.1/0.1 See J-28 Enabled 6.4.1
 0176 Manual torque boost #3 0.0 30.0 [%] 0.1/0.01 See J-28 Enabled 6.4.1
 0177
Motor overload protection level #3
10 100 [%] 1/0.01 100 Enabled 6.4.1
 0178 Base frequency #4 25.0 400.0 [Hz] 0.01/0.01 60.0 Enabled 6.4.1
 0179 Base frequency voltage #4 0.0 600.0 [V] 0.1/0.1 See J-28 Enabled 6.4.1
 0180 Manual torque boost #4 0.0 30.0 [%] 0.1/0.01 See J-28 Enabled 6.4.1
 0181
Motor overload protection level #4
10 100 [%] 1/0.01 100 Enabled 6.4.1
 0182
Motor switching mode selection
0: standard, 1: customized - 0 Disabled / / /
 0183 V/f adjustment coefficient 0 255 1/1 32 Enabled
[6] V/f 5-point setting
Vector control
Title
Communi
cation No
Function Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
To rque
control
Position
control
V/f
Constant
Reference
section
 0190
V/f 5-point setting VF1 frequency
0 400 [Hz] 1/1 0 Disabled 6.5
 0191
V/f 5-point setting VF1 voltage
0 100 [%] 0.1/0.01 0.0 Disabled 6.5
 0192
V/f 5-point setting VF2 frequency
0 400 [Hz] 1/1 0 Disabled 6.5
 0193
V/f 5-point setting VF2 voltage
0 100 [%] 0.1/0.01 0.0 Disabled 6.5
 0194
V/f 5-point setting VF3 frequency
0 400 [Hz] 1/1 0 Disabled 6.5
 0195
V/f 5-point setting VF3 voltage
0 100 [%] 0.1/0.01 0.0 Disabled 6.5
 0196
V/f 5-point setting VF4 frequency
0 400 [Hz] 1/1 0 Disabled 6.5
 0197
V/f 5-point setting VF4 voltage
0 100 [%] 0.1/0.01 0.0 Disabled 6.5
 0198
V/f 5-point setting VF5 frequency
0 400 [Hz] 1/1 0 Disabled 6.5
 0199
V/f 5-point setting VF5 voltage
0 100 [%] 0.1/0.01 0.0 Disabled 6.5
(Reference section): Refer to the inverter's individual manual.