Toshiba VF-A7 Welding System User Manual


 
F-33
[Parameter setting]
Title Function Adjustment range Default setting

Output signal selection of
commercial power/inverter
switching
: OFF
: Automatic switching in case of trip
: Commercial power switching frequency setting
enabled
: Both ( + )

Commercial power/inverter
switching frequency
  [Hz]


Inverter side switching
waiting time
[Model dependent]  [s]
Model
dependent

Commercial power side
switching waiting time
  [s]


Commercial power switching
frequency holding time
  [s]

(*1)The trips which is followed by automatic switching are trips other than , , 
and .
[Timing chart]
Commercial power switching signal S3-CC ON Commercial power operation
Commercial power switching signal S3-CC OFF Inverter operation
Note) If ST-CC is opened,switching cannot be operated normally.
Title Function
Adjustment range
Setting value

Output signal selection of
commercial power/inverter switching
or

Commercial power/inverter switching
frequency
  [Hz]
Power source frequency, etc.

Inverter side switching waiting time
[Model dependent]
 [s]
Model dependent

Commercial power side switching
waiting time
  [s]


Commercial power switching
frequency holding time
  [s]


Input terminal selection #7 (S3)

: (Commercial power
/inverter switching)

Output terminal selection #1 (OUT1)

: (Commercial power
/inverter switching output #1)

Output terminal selection #2 (OUT2)

: (Commercial power
/inverter switching output #2)
Frequency Reference
Commercial power/inverter
switching frequency 
MC output for inverter operation
Commercial power/inv. Switching
output (P24-OUT1)
MC output for commercial
power operation
Commercial power/inv.
switching output (P24-OUT2)
Commercial power switching
signal
Commercial power side switching
waiting time

Inverter side switching
waiting time

Detecting time
Commercial power switching
freq. holding time

ON
ON
Caution!
Before switching to the commercial power, make sure that, when the motor takes power directly from
the commercial power, it rotates in the forward direction as defined for operation by the inverter.
Do not set the Reverse-run prohibition parameter  at or that forward run may be
prohibited. These settings make it impossible to switch the inverter to the forward run position,
and thus to switch from the inverter to the commercial power.
ON
ST (standby) signal