Toshiba VF-A7 Welding System User Manual


 
F-59
6.25.7 Action at low currents
 Low-current trip
 Low-current detection level
 Low-current detection time
  Disabled not trip(FL is not active)
Low-current alarm can be output by output terminal selection.
  Enabled The inverter trips if low-current passes during operation for
the time set with
 or over.(FL is active)
Title Function Adjustment range Default setting

Low-current trip : Disabled, : Enabled

Low-current detection level
  [%]

Low-current detection time
  [s]
6.25.8 Detection of output phase failure
 Detection of output short-circuit during start-up

Adjustment of detection pulse for output short-circuit during start-up
Title Function Adjustment range Default setting

Detection of output short-
circuit during start-up
: Standard
: Only one time at power injection or at
first start after reset

Adjustment of detection pulse
for output short-circuit during
start-up
  [ s] 
 : Standard detecting at starting
A check is made once at the first start of operation after the power is turned on or
the inverter is reset.
 Set the pulse length for the detection of short circuits.
Note) Shorten the pulse length if the motor trips in error (OCL) at start-up, especially a high-speed motor.
6.25.9 Over-torque trip
 Over-torque trip
 Over-torque detection level during power running
 Over-torque detection level during regeneration
 Over-torque detection time
Function
If the current is lower than  level and passes for a time longer than , the
inverter trips. When
 is set at (tripping disabled), it is necessary to set, with
, the time elapsed before the inverter trips after the detection of a small current.
Function
If a torque current exceeding the current set with ,  is detected, the inverter
trips and the trip message  is displayed.
Function
The function is to detect short circuits with inverter's output terminals.