[3] Terminal function selection (2/2)
Vector control
Title
Communi
cation No
Function Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
To rque
control
Position
control
V/f
Constant
Reference
section
 0121
Input terminal selection #11 (B10)
0 135 0 Disabled / / / 7.2.1
 0122
Input terminal selection #12 (B11)
0 135 0 Disabled / / / 7.2.1
 0123
Input terminal selection #13 (B12)
0 135 0 Disabled / / / 7.2.1
 0124
Input terminal selection #14 (B13)
0 135 0 Disabled / / / 7.2.1
 0125
Input terminal selection #15 (B14)
0 135 0 Disabled / / / 7.2.1
 0126
Input terminal selection #16 (B15)
0 135 0 Disabled / / / 7.2.1
 0130
Output terminal selection #1 (OUT1)
0 119 4(LOW) Disabled / / / 7.2.2
 0131
Output terminal selection #2 (OUT2)
0 119 6(RCH) Disabled / / / 7.2.2
 0132
Output terminal selection #3 (FL)
0 119 10(FL) Disabled / / / 7.2.2
 0133
Output terminal selection #4 (R1)
0 119 0 Disabled / / / 7.2.2
 0134
Output terminal selection #5 (R2)
0 119 2 Disabled / / / 7.2.2
 0135
Output terminal selection #6 (OUT3)
0 119 8 Disabled / / / 7.2.2
 0136
Output terminal selection #7 (OUT4)
0 119 14 Disabled / / / 7.2.2
[4] Terminal response time setup
Vector control
Title
Communi
cation No
Function Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
To rque
control
Position
control
V/f
Constant
Reference
section
 0140
Input terminal #1 response time(F)
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0141
Input terminal #2 response time(R)
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0142
Input terminal #3 response time(ST)
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0143
Input terminal #4 response time(RES)
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0144
Input terminal #5-#8 response time
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0145
Input terminal #9-#16 response time
2 to 200 [ms] (in steps of 2.5 [ms]) (*1) 8 Disabled / / / 7.2.3
 0150
Output terminal #1 delay time (OUT1)
(*1) 2 Disabled / / / 7.2.3
 0151
Output terminal #2 delay time (OUT2)
(*1) 2 Disabled / / / 7.2.3
 0152
Output terminal #3 delay time (FL)
(*1) 2 Disabled / / / 7.2.3
 0153
Output terminal #4 delay time
(*1) 2 Disabled / / / 7.2.3
 0154
Output terminal #5 delay time
(*1) 2 Disabled / / / 7.2.3
 0155
Output terminal #6 delay time
(*1) 2 Disabled / / / 7.2.3
 0156
Output terminal #7 delay time
2 to 200 [ms] (in steps of 2.5 [ms])
(*1) 2 Disabled / / / 7.2.3
 0160
Output terminal #1 holding time (OUT1)
(*1) 2 Disabled / / / 7.2.3
 0161
Output terminal #2 holding time (OUT2)
(*1) 2 Disabled / / / 7.2.3
 0162
Output terminal #3 holding time (FL)
(*1) 2 Disabled / / / 7.2.3
 0163
Output terminal #4 holding time
(*1) 2 Disabled / / / 7.2.3
 0164
Output terminal #5 holding time
(*1) 2 Disabled / / / 7.2.3
 0165
Output terminal #6 holding time
(*1) 2 Disabled / / / 7.2.3
 0166
Output terminal #7 holding time
2 to 200 [ms] (in steps of 2.5 [ms])
(*1) 2 Disabled / / / 7.2.3
(*1) The minimum setting unit is 1 ms, but that of response time is 2.5 ms. Input the value which omitted below the decimal point of a multiple of 2.5.
Sensorless vector/vector with sensor ( valid, :invalid)