F-61
6.25.12 Over-voltage stall protection level
Over-voltage stall protection level(high response)
Over-voltage stall protection level
Refer to 6.13.5 for details.
6.25.13 Under-voltage trip
Under-voltage trip mode
Under-voltage detection time
Disabled Inverter stops, but does not trip.(FL is not active)
Enabled The inverter trips if an under-voltage passes for the time
set with
or over. (FL is active)
Title
Function
Adjustment range Default setting
Under-voltage trip mode : Disabled, : Enabled
Under-voltage detection time [s]
6.25.14 UV stall level
Under-voltage stall level
Title
Function
Adjustment range Default setting
Under-voltage stall level
[%]
6.25.15 System-supporting sequence (B-timer)
System-supporting sequence (B-timer)
Title
Function
Adjustment range Default setting
System-supporting sequence (B-timer)
: Invalid
[s]
Function
This parameter is to select the action when detecting an under-voltage. (Invalid, while the
inverter stops.) If is set at (Enabled), it is necessary to set, with , the time
elapsed before the inverter trips after the detection of an under-voltage.
Function
This parameter is used to set the operation level of the regenerative power
ride-through control and the deceleration stop. (Refer to 6.13.2)
Function
This parameter is used to set the waiting time for answer from system(Input terminal function
setting: System-supporting sequence (BA:,) ). After start of operation, if no answer
is received in set time(), the inverter trips().