121
Speed setting by external terminals
4
PARAMETERS
(3) Jog operation from PU
Enable the JOG operation mode using the operation panel and PU (FR-PU07) under speed control. Operation is
performed only while the start button is pressed.
Operation Display
1. Confirmation of the operation status indicator and
operation mode indicator
The monitor mode should have been selected.
The drive unit should be at a stop.
2. Press to choose the PU Jog operation
mode.
3. Press .
While is pressed, the motor rotates.
The motor runs at 150r/min. (Pr.15 initial value)
Hold down.
4. Release
Release
[When changing the speed of PU Jog operation]
5. Press to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously
appears.)
6. Turn until Pr.15 Jog speed setting appears.
7. Press to show the currently set value.
(150r/min)
8. Turn to set the value to " ".
(300r/min)
9. Press to set.
Flicker...Parameter setting complete!!
10.Perform the operations in steps 1 to 4.
The motor rotates at 300r/min.
Three-phase AC
power supply
Drive unit
R/L1
S/L2
T/L3
U
V
W
Operation panel
Motor
STOP