232
Communication operation and setting
Real time monitor
Refer to page 156 for details of the monitor description.
When Pr.37 = "0.01 to 9998", displayed in integral number.
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
Parameter
b15 b0
RES MRS RH RM RL STR STF
b15 b0
ABC FU RUN
Parameter Register Parameter Name
Read/
Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list (page
52) for the parameter names.
Read/
Write
The parameter number + 41000 is the register
number.
C2(902) 41902
Terminal 2 speed setting bias
speed
Read/
Write
C3(902)
42092
Terminal 2 speed setting bias
(Analog value)
Read/
Write
The analog value (%) set to C3 (902) is read.
43902
Terminal 2 speed setting bias
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
125(903) 41903
Terminal 2 speed setting gain
speed
Read/
Write
C4(903)
42093
Terminal 2 speed setting gain
(Analog value)
Read/
Write
The analog value (%) set to C4 (903) is read.
43903
Terminal 2 speed setting gain
(Terminal analog value)
Read
The analog value (%) of the voltage applied to the
terminal 2 is read.
C5(904) 41904
Terminal 4 speed setting bias
speed
Read/
Write
C6(904)
42094
Terminal 4 speed setting bias
(Analog value)
Read/
Write
The analog value (%) set to C6 (904) is read.
43904
Terminal 4 speed setting bias
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905) 41905
Terminal 4 speed setting gain
speed (Speed)
Read/
Write
C7(905)
42095
Terminal 4 speed setting gain
(Analog value)
Read/
Write
The analog value (%) set to C7 (905) is read.
43905
Terminal 4 speed setting gain
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
Register Description Unit
40201
Rotation speed/machine speed/output
frequency
1/1/0.01Hz
40202 Output current 0.01A
40203 Output voltage 0.1V
40205
Rotation speed setting/machine speed
setting/output frequency setting
1/1/0.01Hz
40208 Converter output voltage 0.1V
40209 Regenerative brake duty 0.1%
40210
Electronic thermal relay function load
factor
0.1%
40211 Output current peak value 0.01A
40212 Converter output voltage peak value 0.1V
40214 Output power 0.01kW
40215 Input terminal status
40216 Output terminal status
40219 Position pulse
40220 Cumulative energization time 1h
40223 Actual operation time 1h
40224 Motor load factor 0.1%
40225 Cumulative power 1kWh
40226
Position command
[before electronic gear] (lower 4 digits)
40227
Position command
[before electronic gear] (upper 4 digits)
40228
Current position
[before electronic gear] (lower 4 digits)
40229
Current position
[before electronic gear] (upper 4 digits)
40230
Droop pulse
[after electronic gear] (lower 4 digits)
40231
Droop pulse
[after electronic gear] (upper 4 digits)
40236 Ideal speed command r/min
40237 Speed command r/min
40252 PID set point 0.1%
40253 PID measured value 0.1%
40254 PID deviation 0.1%
40261 Motor thermal load factor 0.1%
40262 Drive unit thermal load factor 0.1%
40263 Cumulative power 2 0.01kWh
Register Description Unit