Mitsubishi Electronics FR-E700EX Welder User Manual


 
192
Selection of operation mode and operation location
(10) Switching of operation mode by external signal (X16 signal)
When external operation and operation from the operation panel are used together, use of the PU-External operation
switching signal (X16) allows switching between the PU operation mode and External operation mode during a stop
(during a motor stop, start command OFF).
When Pr.79 = any of "0, 6, 7", the operation mode can be switched between the PU operation mode and External
operation mode. (Pr.79 = "6" At Switchover mode, operation mode can be changed during operation)
For the terminal used for X16 signal input, set "16" to any of Pr.178 to Pr.184 (input terminal function selection) to assign the
function.
(11) Switching of operation mode by external signals (X65, X66 signals)
When Pr.79 = any of "0, 2, 6, 7", the operation mode switching signals (X65, X66) can be used to change the PU or
External operation mode to the Network operation mode during a stop (during a motor stop or start command OFF).
(Pr.79 = "6" Switch-over mode can be changed during operation)
When switching between the Network operation mode and PU operation mode
1)Set Pr.79 to "0" (initial value) or "6".
2)Set "10" in Pr.340 Communication startup mode selection
3)Set "65" in any of Pr.178 to Pr.184to assign the NET-PU operation switching signal (X65) to the terminal.
4)The operation mode changes to the PU operation mode when the X65 signal turns ON, or to the Network operation
mode when the X65 signal turns OFF.
Pr.79
Setting
X16 Signal State Operation Mode
Remarks
ON (External) OFF (PU)
0 (initial value)
External operation
mode
PU operation mode Can be switched to External, PU or NET operation mode
1 PU operation mode Fixed to PU operation mode
2 External operation mode
Fixed to External operation mode (can be switched to NET operation
mode)
3, 4 External/PU combined operation mode External/PU combined mode fixed
6
External operation
mode
PU operation mode
Switching among the External, PU, and NET operation mode is
enabled while running.
7
X12 (MRS)
ON
External operation
mode
PU operation mode
Can be switched to External, PU or NET operation mode (output stop
in External operation mode)
X12 (MRS)
OFF
External operation mode
Fixed to External operation mode (forcibly switched to External
operation mode)
REMARKS
The operation mode status changes depending on the setting of Pr.340 Communication startup mode selection and the ON/OFF
status of the X65 and X66 signals. (For details, Refer to page 192)
The priorities of Pr.79 , Pr.340 and signals are Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
NOTE
Changing the terminal assignment using Pr.178 to Pr.184 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Pr.340
Setting
Pr.79
Setting
X65 Signal State
Remarks
ON(PU) OFF(NET)
10
0 (initial value) PU operation mode NET operation mode Cannot be switched to External operation mode
1 PU operation mode Fixed to PU operation mode
2 NET operation mode Fixed to NET operation mode
3, 4 External/PU combined operation mode External/PU combined mode fixed
6 PU operation mode NET operation mode
Operation mode can be switched with operation
continued
Cannot be switched to External operation mode
7
X12 (MRS)
ON
Switching among the External and
PU operation mode is enabled
Output stop in External operation mode
X12 (MRS)
OFF
External operation mode Forcibly switched to External operation mode
 NET operation mode when the X66 signal is ON.
 PU operation mode is selected when the X16 signal is OFF. PU operation mode also when Pr.550 NET mode operation command source selection = "0"
(communication option command source) and the communication option is not fitted.
 External operation mode when the X16 signal is ON.