Selection of operation mode and operation location
4
PARAMETERS
(5) Selection of command source in Network operation mode (Pr.338, Pr.339)
There are two control sources: operation command source, which controls the signals related to the drive unit start
command and function selection, and speed command source, which controls signals related to speed setting.
In Network operation mode, the commands from the external terminals and communication (PU connector or
communication option) are as listed below.
[Explanation of table]
External : Command is valid only from control terminal.
NET : Command only from communication is valid
Combined: Command from both control terminal and communication is valid.
: Command from either of control terminal and communication is invalid.
Operation
Location
Selection
Pr.338 Communication operation
command source
0: NET 1: External
Remarks
Pr.339 Communication speed
command source
0: NET
1: External 2: External
0: NET
1: External 2: External
Fixed
function
(terminal-
equivalent
function)
Running speed from
communication
NET NET NET NET
Terminal 2
External External
Terminal 4
External External
Selective function
Pr.178 to Pr.184 setting
0RL
Low-speed operation
command/remote setting
clear
NET External NET External
Pr.59 = "0"
(multi-speed)
Pr.59 = "1, 2"
(remote)
1RM
Middle-speed operation
command/remote setting
function
NET External NET External
2RH
High-speed operation
command/remote setting
function
NET External NET External
3 RT Second function selection
NET External
4 AU Terminal 4 input selection
Combined Combined
5 JOG Jog operation selection
External
7OH
External thermal relay
input
External
8 REX 15-speed selection
NET External NET External
Pr.59 = "0"
(multi-speed)
10 X10 Drive unit run enable signal
External
12 X12
PU operation external
interlock
External
14 X14 PID control valid terminal
NET External NET External
16 X16
PU/External operation
switchover
External
23 LX Pre-excitation
NET External
24 MRS
Output stop
Combined External Pr.79 "7"
PU operation interlock
External
Pr.79 = "7"
When the X12
signal is not
assigned
25
STOP
Start self-holding selection
External
29 X29 Stopper control switchover
NET External
30
JOG2
Jog operation selection 2
NET External
44 X44 P/PI control switchover
NET External
60 STF Forward rotation command
NET External
61 STR Reverse rotation command
NET External
62 RES Drive unit Reset
External
65 X65
PU/NET operation
switchover
External
66 X66
External/NET operation
switchover
External
67 X67
Command source
switchover
External
76 X76 Proximity dog
Combined External
86 SON Servo-ON
NET External
87 X87 Position control sudden stop
Combined External
88 LSP Forward stroke end
Combined External
89 LSN Reverse stroke end
Combined External
REMARKS
The command source of communication is as set in Pr.550 and Pr.551.
The Pr.338 and Pr.339 settings can be changed while the drive unit is running when Pr.77 = "2". Note that the setting change is
reflected after the drive unit has stopped. Until the drive unit has stopped, communication operation command source and
communication speed command source before the setting change are valid.