Mitsubishi Electronics FR-E700EX Welder User Manual


 
168
Speed setting by analog input (terminal 2, 4)
4.15 Speed setting by analog input (terminal 2, 4)
4.15.1 Analog input selection (Pr.73, Pr.267)
(1) Selection of analog input specifications
For the terminal 2 for analog voltage input, 0 to 5V (initial value) or 0 to 10V can be selected.
Either voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA initial value) can be selected for terminal 4 used for
analog input.
Change the input specifications to change Pr.267 and voltage/current input switch.
Rated specifications of terminal 4 change according to the voltage/current input switch setting.
Voltage input: Input resistance 10k1k, maximum permissible input voltage 20VDC
Current input: Input resistance 2335, maximum permissible input voltage 30mA
Purpose Parameter to set Refer to page
To select voltage/current input
(terminal 2, 4)
To perform forward/reverse rotation
by analog input
Analog input selection Pr.73, Pr.267
168
To adjust (calibrate) analog input
speed and voltage (current)
Bias and gain of speed setting
voltage (current)
Pr.125, Pr.126, Pr.241,
C2 to C7 (Pr.902 to Pr.905)
173
You can select the function that switches between forward rotation and reverse rotation according to the analog input
terminal specifications and input signal.
Parameter
number
Name
Initial
value
Setting
range
Description
73 Analog input selection
1
0 Terminal 2 input 0 to 10V Without reversible
operation1 Terminal 2 input 0 to 5V
10 Terminal 2 input 0 to 10V
With reversible operation
11 Terminal 2 input 0 to 5V
267
Terminal 4 input
selection
0
Voltage/current input
switch
Description
0 Terminal 4 input 4 to 20mA
1 Terminal 4 input 0 to 5V
2 Terminal 4 input 0 to 10V
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)
Control circuit terminal block
Current input (initial setting)
Voltage input