221
Communication operation and setting
4
PARAMETERS
[Multi command (HF0)]
Sending data format from computer to drive unit
Reply data format from drive unit to computer (No data error detected)
 Specify the data type of sending data (from computer to drive unit). When specifying data type 4, set 4 for both the sending data and reply data.
 Specify the data type of reply data (from drive unit to computer). When specifying data type 4, set 4 for both the sending data and reply data.
 Combination of data 1 and data 2 for sending
 Combination of data 1 and data 2 for reply
 Error code for sending data 1 is set in error code 1, and error code for sending data 2 is set in error code 2.
Mode error (HA), instruction code error (HB), data range error (HC) or no error (HF) is replied.
Format
Number of Characters
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A3
ENQ
Drive unit
station
number
Instruction
Code
(HF0)
Waiting
time
Send
data
type

Receive
data
type

Data1  Data2 
Sum check CR/LF
Format
Number of Characters
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
C1
STX
Drive unit
station
number
Send
data
type

Receive
data
type

Error
code 1

Error
code 2

Data1  Data2 
ETX Sum check CR/LF
Data Type Data 1 Data 2 Remarks
0
Run command (expansion) Set speed (RAM)
Run command (expansion) is same as instruction
code HF9 (Refer to page 219)
The unit of set speed (frequency) is always by
four digits, even when "0.01 to 9998" is set in
Pr.37 and "01" is set in instruction code HFF.
1
Run command (expansion) Set speed (RAM, EEPROM)
4
H00 + monitor code 1 H00 + monitor code 2
Set a special monitor selection No. in monitor
code 1 and 2. (Set 00 in the upper two digits.)
Data Type Data 1 Data 2 Remarks
0
Drive unit status monitor
(expansion)
Rotation speed
(output frequency)
Drive unit status monitor (expansion) is same as
instruction code H79 (Refer to page 220)
The unit of speed (frequency) monitor is always
by four digits (rounds down after the decimal
point), even when "0.01 to 9998" is set in Pr.37
and "01" is set in instruction code HFF.
Replys the monitor item specified in instruction
code HF3 for special monitor. (Refer to page 218)
1
Drive unit status monitor
(expansion)
Special monitor
4
First monitor value Second monitor value
The first monitor value and second monitor value
store the monitor data specified by the sending
data type 4.
When the sending data type is not 4, the first
monitor value stores the current monitor and the
second monitor value stores the rotation speed
monitor.
The unit of speed (frequency) monitor is always
by four digits (rounds down after the decimal
point), even when "0.01 to 9998" is set in Pr.37
and "01" is set in instruction code HFF.