Monitor display and monitor output signal
4
PARAMETERS
(2) How to calibrate the terminal FM when using the operation panel
Operation Display
1.
Confirmation of the operation status indicator
and operation mode indicator
(When Pr.54 = 1)
2. Press to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously appears.)
3. Turn until appears.
4. Press to display .
5. Turn until appears.
Set to C0 FM terminal calibration.
6. Press to enable setting.
7. If the drive unit is at a stop, press the
key to start the drive unit.
8. Turn to adjust the indicator needle to the
desired position.
Analog indicator
9. Press .
Setting is complete.
Flicker...Parameter setting complete!!
Turn to read another parameter.
Press to return to the indication (step 4).
Press twice to show the next parameter ( ).
REMARKS
Calibration can also be made for external operation. Set the speed in the External operation mode, and make calibration in the
above procedure.
Calibration can be made even during operation.
For operation from the parameter unit (FR-PU07), refer to the instruction manual of the parameter unit.
Parameters referred to
Pr.54 FM terminal function selection Refer to page 155
Pr.55 Speed monitoring reference Refer to page 161
Pr.56 Current monitoring reference Refer to page 161
C0 to C7 setting
is enabled.
The monitor set to
Pr. 54 FM terminal function
selection is displayed.