Mitsubishi Electronics BNP-C3040D Welder User Manual


 
5. Spindle Adjustment
5 - 4
5-1-3 Setting the output magnification
(1) Meter output (Data No. 0)
With meter output, the output channel is fixed, and the output voltage range is 0 to 10V in the
positive range. Set the magnification with the following parameters. Also, low path filter can be set
on the load meter output.
No. Abbr. Parameter name Details
Setting
range
Standard
SP017 TSP* Maximum motor
speed
Set the maximum spindle motor speed.
When SP249=0, the motor speed will be the motor rotation
speed at the speedometer 10V output.
1 to 32767
(r/min)
6000
SP094 LMAV* Load meter output
filter
Set the filter time constant of load meter output.
When "0" is set, a filter time constant is set to 100ms.
0 to 32767
(2ms)
0
SP249 SMO Speedometer speed Set the motor rotation speed when the speedometer 10V is
output.
When set to "0", this parameter becomes the same as SP017
(TSP).
0 to 32767
(r/min)
0
SP250 LMO Load meter voltage Set the voltage when the load meter 120% is output. When set
to "0", this becomes 10V.
0 to 10
(V)
0
(2) Internal data output (Data No. 1 to 13)
Normally, the standard setting value is set for the output magnification (SP255, SP256). When
"0" is set, the magnification will be the same as "256".
DATA ×
SP255
256
×
10 [V]
256
(
8 bit
)
+ 5 [V] (offset) = Output voltage [V]
(Example) To output current FB at a 30-minute stall rating 20%/V unit (SP253=3, SP255=8)
819.2 ×
8
256
×
10
256
+ 5 = 6 [V]
No. Abbr. Parameter name Details
Setting
range
Standard
SP255 DA1MPY DA output channel 1
magnification
0
SP256 DA2MPY DA output channel 2
magnification
Set the output magnification with a 1/256 unit.
When "0" is set, the magnification will be the same as "256".
-32768 to
32767
(1/256-fold)
0